Grant: Engage Grants Program
University of Western Ontario
$24,942.00
Understanding the cracking phenomena of stainless steel steam condensate piping and developing mitigation methodologies to minimize cracking
EF 2012-13
Résumé
Veresen Inc. is a Canadian-investor owned company which owns and operates energy infrastructure assets
across North America. London District Energy (LDE) in London Ontario is one of its subsidiaries and has been
providing heating and cooling services to over 60 municipal, public and private clients in downtown London
for more than 100 years. As such, this company serves 15% of downtown heating and cooling needs.
This proposal deals with the failure of the 3 km long 304 stainless steel piping between the LDE Plant and
St. Joseph's Hospital. High pressure steam travels through 12"" diameter steel piping and the return steam
condensate through 4"" diameter piping. Both are insulated with glass foam insulation and wrapped with a
waterproof jacket and buried under city streets, except for locations at the concrete vaults under the manhole
covers where the pipes could be exposed to the outside environment. There have been no corrosion issues with
the steam line (~425 °F) but the return steam condensate line (~ 185 °F) is exhibiting extensive cracking and
rupture inside the concrete vault where the piping is exposed to the surroundings. LDE currently is replacing
cracked sections by cutting out the affected pipe and welding in a new section. The number of failures has
recently increased and, in some cases, on replacement sections within two months after replacement. Clearly,
replacement of a section is not an enduring solution and an understanding of the factors causing cracking is
needed to alleviate this issue. It is anticipated that an alternative replacement material will be required for an
enduring solution. Hence the suitability of some of the higher grade austenitic and duplex stainless steels for
this application will also be investigated in this study. Thus, the proposed research methodology is expected to
provide LDE some solutions to the cracking issue under the manhole covers.
Future extensive collaborative work will address the cracking issue at the buried underground locations and
how specific materials would respond to the unique challenges at both locations. The results from this project
will define the work scope for the extensive collaborative research.
Programme
Engage Grants Program
Bénéficiaire
Emplacement
Ontario, Canada
Type de bénéficiaire
Academia
Type
Grant
Source
NSERC's Awards Data
Tel que publié
Application id
434655-2012
Name nom
Shoesmith, David
Department département
Chemistry
Organization id
36
Institution établissement
University of Western Ontario
Province en
Ontario
Province fr
Ontario
Country en
CANADA
Country fr
CANADA
Fiscal year exercice financier
2012
Competition year année de concours
2012
Award amount
24942
Program id
EGP
Program name en
Engage Grants Program
Program name fr
Programme de subventions d'engagement partenariat
Group en
Research partnerships programs
Group fr
Programmes de partenariat
Committee code
1553
Committee name en
Ontario Internal Decision Committee
Committee name fr
Comité de décision interne pour l'Ontario
Area of application code
602
Area of application group en
Construction, urban and rural planning
Area of application group fr
Construction, urbanisme et aménagement rural
Area of application en
Materials performance
Area of application fr
Performance des matériaux
Research subject code
2001
Research subject group en
Materials science and technology
Research subject group fr
Science et technologie des matériaux
Research subject en
Materials structure, properties and testing
Research subject fr
Structure, propriétés et essais des matériaux
Partie
1
Nb partie
1
Application title
Understanding the cracking phenomena of stainless steel steam condensate piping and developing mitigation methodologies to minimize cracking
Keyword
NSERC
Application summary
Veresen Inc. is a Canadian-investor owned company which owns and operates energy infrastructure assets
across North America. London District Energy (LDE) in London Ontario is one of its subsidiaries and has been
providing heating and cooling services to over 60 municipal, public and private clients in downtown London
for more than 100 years. As such, this company serves 15% of downtown heating and cooling needs.
This proposal deals with the failure of the 3 km long 304 stainless steel piping between the LDE Plant and
St. Joseph's Hospital. High pressure steam travels through 12"" diameter steel piping and the return steam
condensate through 4"" diameter piping. Both are insulated with glass foam insulation and wrapped with a
waterproof jacket and buried under city streets, except for locations at the concrete vaults under the manhole
covers where the pipes could be exposed to the outside environment. There have been no corrosion issues with
the steam line (~425 °F) but the return steam condensate line (~ 185 °F) is exhibiting extensive cracking and
rupture inside the concrete vault where the piping is exposed to the surroundings. LDE currently is replacing
cracked sections by cutting out the affected pipe and welding in a new section. The number of failures has
recently increased and, in some cases, on replacement sections within two months after replacement. Clearly,
replacement of a section is not an enduring solution and an understanding of the factors causing cracking is
needed to alleviate this issue. It is anticipated that an alternative replacement material will be required for an
enduring solution. Hence the suitability of some of the higher grade austenitic and duplex stainless steels for
this application will also be investigated in this study. Thus, the proposed research methodology is expected to
provide LDE some solutions to the cracking issue under the manhole covers.
Future extensive collaborative work will address the cracking issue at the buried underground locations and
how specific materials would respond to the unique challenges at both locations. The results from this project
will define the work scope for the extensive collaborative research.